Q.1. Why all overhead lines use ACSR conductors?
Power System - I
22 questions
Q.2. Why we use Vacuum Circuit Breaker in High Transmission System and not Air Circuit Breaker?
Q.3. Why HVDC line do not require any reactive power compensation?
Q.4. What are the advantages of adopting EHV/UHV for transmission of AC electric power?
Q.5. What will happen when power factor is leading in distribution of power?
Q.6. What is infinite bus in power system?
Q.7. What is the difference between Isolator and Circuit Breaker?
Q.8. How can we reduce the effect of corona?
Q.9. What is the difference between grid station and substation?
Q.10. For a fault at a given location, rank the various faults in the order of severity.
Q.1. Two generators rated 10MVA, 13.2kV and 15MVA, 13.2kV are connected in parallel to a bus bar. They feed supply to 2 motors of inputs 8MVA and 12MVA respectively. The operating voltage of motors is 12.5kV. Assuming the base quantities as 50MVA, 13.8kV, draw the per unit reactance diagram. The percentage reactance for generators is 15% and that for motors is 20%.
Q.2. Derive the expression for the capacitance of three phase unsymmetrical spaced transposed overhead transmission line.
Q.3. Discuss series and shunt compensation of a transmission line.
Q.4. Write short notes on the following: (a) Insulation coordination (b) Radial and mesh distribution networks.
Q.5. Draw a simple scheme of HVDC converter station and describe briefly components of the converter station.
Q.6. A synchronous motor, having a power consumption of 50kW, is connected in parallel with a load of 200kW, 0.8 p.f. lagging. The excitation of the motor is adjusted until combined power factor becomes 0.9 lagging. Determine the kVA input and power factor of synchronous motor.
Q.7. Differentiate between synchronous and asynchronous grid.
Q.1. (a) Define the term feeder, distributor and service mains.
(b) What is the percentage saving in feeder copper, if the line voltage in a 2-wire DC system is raised from 250 volts to 500 volts for the same transmitted power over the same distance and having equal power loss?
Q.2. (a) Explain different types of AC transmission line. Derive the expression of ABCD constants for nominal T configured Medium Transmission line.
(b) The ABCD line constant of a 220 kV line are: A = D = 0.94∠1°; B = 130∠73°; C = 0.001∠90°. If the sending end voltage (Vs) of the line for a given load delivered at nominal voltage is 240kV, then determine % voltage regulation of line.
Q.3. (a) Derive an expression for fault current for double line-to-ground (LLG) fault by Symmetrical Components Method.
(b) A 3-phase, 11kV, 10MVA alternator has sequence reactances of X0 = 0.05 p.u., X1 = 0.15 p.u. and X2 = 0.15 p.u. If the generator is on no load, find the ratio of fault currents for L-G fault to that when all the 3-phases are dead short-circuited.
Q.4. (a) What is the difference between On-grid and Off-grid solar power?
(b) Discuss in detail the principle of DC Link control.
Q.5. (a) Explain the working of SF6 gas circuit breaker.
(b) An 11kV, 3-phase transmission line has a resistance of 1.5 ohm and reactance of 4 ohm per phase. Calculate the percentage regulation and efficiency of the line when a total load of 5000kVA at 0.8 lagging power factor is supplied at 11kV at the distant end.