RTUEE / EC / EEEYr 2023 · Sem 52023

Q1Power System - I

Question

15 marks

Q.1. (a) Define the term feeder, distributor and service mains.

(b) What is the percentage saving in feeder copper, if the line voltage in a 2-wire DC system is raised from 250 volts to 500 volts for the same transmitted power over the same distance and having equal power loss?

Answer

A feeder carries bulk power without tapped loads, a distributor has loads tapped along its length, and service mains connect an individual consumer's premises to the nearest distributor; raising a 2-wire DC system's voltage from 250V to 500V for the same power/loss/distance gives a 75% saving in feeder copper, since conductor volume varies inversely as the square of the voltage.

(a) Feeder, Distributor and Service Mains

A feeder is a conductor that carries electrical power in bulk from the substation/generating station to a distributor or load center, without having any consumer service connections tapped off along its route, so its current-carrying capacity (not voltage drop) is the primary design criterion, since the current in a feeder is constant along its full length. A distributor is a conductor from which numerous individual consumer service connections are tapped off at various points along its length to supply electricity directly to consumers; unlike a feeder, the current in a distributor progressively decreases along its length as loads are tapped off, and the primary design consideration is the permissible voltage drop to the farthest-connected consumer (since cumulative voltage drop, not simple current-carrying capacity, becomes the limiting factor). Service mains are the final short conductors connecting an individual consumer's premises (their meter/service point) to the nearest distributor, carrying only that single consumer's load current.

(b) Percentage Saving in Feeder Copper (Voltage Raised 250V to 500V)

For a 2-wire DC feeder transmitting the same power P over the same distance l with the same percentage power loss, the volume of copper required is inversely proportional to the square of the transmission voltage. This is derived as follows: with current I = P/V, and loss = 2I²R = 2(P/V)²R; for a fixed permissible loss, R ∝ V²/P² (for fixed P), and since R = ρl/a, the conductor cross-section a ∝ 1/R ∝ P²/V², so the total copper volume (Vol = 2×a×l) ∝ 1/V² for a fixed P and l.

So the copper volume required at 500 V is only 25% of that required at 250 V, giving a percentage saving of:

This large saving (75%) is precisely the economic reason why power systems are transmitted at progressively higher voltages as distance and power level increase: doubling the voltage reduces the required conductor copper (and hence weight, cost, and supporting structure requirements) to just a quarter of its previous value for the same power delivered with the same percentage loss over the same distance.

Extended Discussion: Feeder, Distributor and Service Mains in Practical Networks

In a typical urban low-voltage distribution scheme, the physical hierarchy runs: a distribution transformer (fed by an 11 kV primary feeder) steps down to 415 V/230 V, from which an LT feeder carries this stepped-down bulk power (without any consumer taps) to the start of a residential/commercial street; a distributor then runs along the street with individual consumer service connections tapped off progressively along its length; and the short final service-main conductor connects the distributor's nearest tap point to each individual consumer's meter board. Because a feeder carries a constant current along its whole length, feeder conductors are sized purely on current-carrying (thermal) capacity, and the voltage drop along a feeder is simply IR+IX(sinφ terms) computed once for the known, constant current. A distributor's design is fundamentally different: since the current tapped off progressively decreases along its length, the cumulative voltage drop to the last (farthest) consumer is what must be kept within the statutory limit (commonly ±6% of nominal utilisation voltage in Indian practice), and distributor conductor sizing is therefore an economic trade-off between conductor cost and the permissible cumulative drop, often requiring different, tapering conductor sizes along the distributor's length in more sophisticated designs (though uniform-section distributors are more common in practice for simplicity of stocking and installation).

Extended Discussion: General n-Fold Voltage Scaling and Percentage Saving

The specific 75% saving computed above for a voltage doubling (250 V to 500 V) generalizes to any voltage ratio k = V2/V1 as follows, using the same equal-power, equal-loss, equal-distance derivation:

For example, tripling the voltage (k=3) would give a saving of (1-1/9)×100% = 88.9%, and raising the voltage tenfold (k=10, characteristic of stepping from a distribution to a transmission voltage class) would give a saving of 99%, showing why bulk long-distance transmission is always carried out at the highest practical voltage level the insulation and switchgear technology of the day can economically support — the copper/aluminium savings from voltage escalation are so large that they dominate the overall economics of transmission line design even after accounting for the increased cost of higher-voltage insulation, towers and switchgear.

Numerical verification using the direct current/resistance route: for P=constant and loss=constant, current I1=P/V1=P/250 and I2=P/V2=P/500=I1/2. Loss1=2I1²R1 and Loss2=2I2²R2; setting Loss1=Loss2 gives R2=R1×(I1/I2)²=R1×4, so R2=4R1. Since R=ρl/a with the same ρ and l, a2=a1/4, giving Vol2/Vol1 = (2×a2×l)/(2×a1×l) = a2/a1 = 1/4, exactly matching the (V1/V2)² general-formula result above and confirming the correctness of the 75% saving figure via an entirely independent derivation route starting from first-principles current and resistance relations rather than the direct voltage-ratio-squared shortcut.

It should be noted that this idealized copper-saving calculation assumes the transmitted power, distance, and percentage loss are all held exactly constant while only the voltage is changed; in a real system, raising the transmission voltage also requires re-evaluating insulation clearances, tower/pole height and strength, transformer costs at both ends, and safety clearances from ground and other structures — all of which increase with voltage — so the actual overall economic optimum voltage for a given transmission task balances the quadratically-diminishing conductor cost against the increasing insulation/structural cost, rather than simply selecting the highest voltage that yields the largest theoretical copper saving.

This same inverse-square relationship between conductor volume and transmission voltage is the identical principle underlying the classical economic-voltage (Kelvin's Law-type) analysis used to determine the most cost-effective transmission voltage for a given power and distance: as voltage increases, annual conductor cost (proportional to 1/V²) falls sharply while annual cost of insulation, switchgear and transformers (which rises with voltage, though less steeply) increases, and the total annual cost curve exhibits a minimum at an intermediate 'most economical transmission voltage,' beyond which any further voltage increase, despite continuing to reduce conductor cost, is outweighed by the faster-growing insulation/equipment cost — precisely the qualitative trade-off invoked in the closing remark of the discussion above, generalized here into the standard technique used in transmission system planning to select the voltage level for a new line or corridor.

Historically, this exact percentage-saving calculation (250 V to 500 V DC) reflects the early era of DC electricity distribution (Edison-style low-voltage DC networks), where the practical maximum feeder voltage was tightly constrained by consumer appliance/lamp insulation ratings and by the absence of any simple DC voltage-transformation device; the large conductor saving achievable simply by permitting a higher distribution voltage was one of the strongest early arguments in the historic AC-versus-DC ('War of Currents') debate favoring AC distribution, since AC's easy transformer-based voltage step-up allowed transmission at voltages far beyond what a DC feeder of that era could economically or safely support at the consumer end, ultimately leading to AC becoming the near-universal standard for public electricity supply.

Back to Paper