RTUEE / EC / EEEYr 2020 · Sem 82020

Q3Protection of Power System

Question

16 marks

Q.3. (a) Explain loss of excitation protection scheme and unbalanced loading protection. [8]

(b) Explain prime mover protection scheme for a generator with reverse power relay operating characteristics. [8]

Answer

As discussed in relation to another question in this examination, loss of excitation causes a generator to fall out of synchronism and to begin drawing reactive power from the connected system instead of supplying it, with the generator's operating point, viewed on the R-X impedance plane as seen by relaying equipment at the generator terminals, moving from its normal operating region (typically in the fourth quadrant of the R-X plane, corresponding to the generator exporting both active and reactive power) into a characteristic locus that enters and settles within a circle in the impedance plane whose diameter is approximately equal to the generator's synchronous reactance Xd, offset below the resistance (R) axis by approximately half the generator's transient reactance Xd-prime. This distinctive impedance-plane signature forms the basis of the standard loss of excitation protection scheme, which uses an offset mho-type distance relay (an impedance relay whose circular operating characteristic on the R-X plane is deliberately offset from the origin to match the specific locus that the loss-of-excitation impedance trajectory follows) connected to measure the impedance at the generator terminals; when the measured impedance enters and remains within this offset mho characteristic circle for a set time delay (the time delay is included specifically to avoid unwanted tripping during transient stability swings or other temporary system disturbances that might briefly cause the measured impedance to pass through, without remaining within, the same region of the R-X plane), the relay operates to trip the generator, since sustained presence within this specific impedance region reliably indicates an actual, sustained loss of excitation condition rather than a transient system disturbance.

Unbalanced Loading Protection

As discussed in relation to another question in this examination, unbalanced stator loading produces negative-sequence stator currents, which induce damaging double-supply-frequency currents in the rotor body and damper windings, causing severe localized rotor surface heating that can rapidly exceed the rotor's thermal withstand capability if sustained. Unbalanced loading protection is provided by a negative-sequence overcurrent relay, which uses a sequence current filter (a network that extracts specifically the negative-sequence component from the three-phase stator currents, rejecting the positive- and zero-sequence components) to derive a signal proportional to the negative-sequence current magnitude, and operates according to a thermal-inverse-time characteristic of the general form I2-squared times t equals a constant (K), reflecting the fact that rotor surface heating from induced double-frequency currents is proportional to the square of the negative-sequence current magnitude, closely mirroring the actual thermal withstand capability of the generator rotor as documented by the generator manufacturer; this inverse-square-law time characteristic allows the relay to tolerate brief, modest negative-sequence current excursions (such as those caused by a remote, quickly cleared external unbalanced fault) without tripping, while still reliably tripping within an appropriately short time for a more severe or sustained unbalanced condition that would otherwise cause the rotor's permissible thermal withstand limit to be exceeded.

Prime Mover Protection with Reverse Power Relay

As discussed in relation to another question in this examination, a loss of prime mover input power, if left undetected, causes the generator to begin motoring, drawing mechanical power from the connected electrical system to continue driving its own unpowered prime mover; this reversal of the normal power flow direction (from the generator supplying power to the system, to the system instead supplying power to drive the generator as a motor) is precisely what a reverse power relay is designed to detect. A reverse power relay is a directional power relay that continuously monitors the direction (sign) of real power flow at the generator terminals, connected to sense both the generator's terminal voltage and current, and calibrated to operate specifically when real power flow reverses direction (from the normal generating direction to the reversed, motoring direction) and exceeds a small, carefully set threshold magnitude, since only a relatively small amount of reverse power (a few percent of the generator's rated capacity) is typically drawn during actual motoring, corresponding to the modest mechanical losses (windage and friction) of the now-unpowered prime mover that the electrical system must supply to keep the generator-turbine set rotating.

The operating characteristic of a reverse power relay is typically represented on a power-angle or real-power-versus-reactive-power plane as a straight line (or a narrow band) passing close to, but offset from, the origin on the reverse-power side, with the relay set to operate whenever the measured real power falls below this small negative (reverse) threshold value; a deliberate time delay (commonly in the range of a few seconds up to a minute or more, depending on the specific prime mover type and its sensitivity to motoring operation) is included in the reverse power protection scheme, since brief, transient reversals of power flow can occur during certain normal system transients or during generator synchronizing operations without indicating a genuine sustained loss of prime mover condition, and an overly fast-operating reverse power relay would risk unwanted tripping during these harmless transient conditions; the time delay is set short enough, however, to trip well before the specific prime mover type's own thermal or mechanical damage threshold for sustained motoring operation is reached, with steam turbine prime movers generally requiring a shorter permissible motoring time (due to the turbine blade overheating risk from inadequate steam flow cooling during motoring) than diesel engine or gas turbine prime movers, whose reverse-power protection time delay settings are typically chosen accordingly less restrictively.

It is further worth noting that all three of the abnormal generator operating conditions addressed in this question, loss of excitation, unbalanced loading, and prime mover failure, share a common underlying protection philosophy despite their differing physical causes: each condition is detected not through a simple fixed-threshold overcurrent measurement (which would be poorly suited to detecting these specific, more subtle abnormal conditions) but instead through a measurement quantity specifically tailored to the physical signature of that particular abnormal condition, namely offset impedance for loss of excitation, negative-sequence current for unbalanced loading, and reversed real power flow for prime mover failure, illustrating the general principle that effective generator protection requires a suite of specialized protection functions, each targeted at a specific failure mode, rather than relying on generic overcurrent protection alone.

Back to Paper