RTUEE / EC / EEEYr 2019 · Sem 72019

Q9Power System Engineering

Question

16 marks

5. (a) Discuss the method of voltage control in power system using tap changing transformers. [8]

(b) Define normal operating state, emergency operating state and restorative operating state of power system. [8]

Answer

(a) Voltage Control Using Tap Changing Transformers

A tap changing transformer provides voltage control by allowing the effective turns ratio between its primary and secondary windings to be adjusted, typically by connecting the winding tap point to one of several discrete taps provided along the winding at different points, each tap corresponding to a slightly different number of active turns and hence a slightly different transformation ratio - by selecting a tap that increases or decreases the effective turns ratio, the transformer's secondary-side output voltage can be raised or lowered relative to a fixed primary-side voltage, compensating for voltage variations caused by changing load conditions elsewhere in the system.

Tap Changing Transformer (schematic)Primary windingSecondaryTap selector

Two broad categories of tap changing are used in practice: off-load (no-load, off-circuit) tap changers, which require the transformer to be de-energized (disconnected from the system) before the tap position can be changed, suitable only for occasional, infrequent voltage adjustment (such as compensating for a seasonal or long-term change in average system voltage), since taking a transformer out of service each time a tap change is needed is impractical for frequent voltage regulation; and on-load tap changers (OLTC), which can change tap position while the transformer remains fully energized and carrying load current, using a specially designed switching mechanism (typically involving a transitional/bridging impedance to briefly connect two adjacent taps together momentarily during the changeover, preventing the tap-changing switch contacts from ever having to interrupt the full load current directly across an open tap gap) - on-load tap changers are far more widely used in practice for automatic, continuous voltage regulation, since they can respond to changing load conditions throughout the day without requiring the transformer to be taken out of service.

In practical application, on-load tap changing transformers are typically installed at key points in the transmission and distribution network (at bulk supply substations feeding distribution networks, and sometimes at generator step-up transformers or interconnecting transformers between different voltage levels), with the tap position automatically adjusted by an automatic voltage regulator relay that continuously monitors the secondary-side voltage and commands a tap change whenever the measured voltage departs from its desired setpoint band by more than a specified deadband amount for longer than a specified time delay (the delay being important to avoid excessive, rapid tap-changing operations, called 'hunting', in response to normal short-term load fluctuations, since each tap-change operation causes some mechanical wear on the tap-changer's switching contacts).

Tap changing transformers are a particularly cost-effective and widely deployed voltage control technique because they directly address the voltage-drop problem caused by varying load current flowing through the transformer's own leakage impedance and the connected feeder's impedance, without requiring any separate reactive power compensation equipment (shunt capacitors, synchronous condensers, or SVC/STATCOM devices, discussed elsewhere in this examination) - however, tap changing alone adjusts voltage magnitude at a single point without directly controlling reactive power flow throughout the wider network, meaning tap changing transformers are typically used in combination with, rather than as a complete substitute for, other reactive power compensation techniques in a comprehensive power system voltage control strategy.

(b) Operating States of a Power System

The normal operating state is the condition in which the power system is operating with all load demands satisfied, all equipment operating within its rated limits (voltage, current, frequency all within acceptable bounds), and with sufficient reserve capacity and adequate security margin such that the system could withstand the loss of any single major element (an N-1 contingency, such as a generator or transmission line outage) without violating any operating limit or causing cascading failure - this is the desired, target operating condition for a power system under essentially all circumstances.

The emergency operating state occurs when one or more system operating limits are already being violated (equipment overloaded, or voltage/frequency outside acceptable bounds), typically as the result of a significant contingency (major equipment failure or unexpectedly severe load/generation imbalance) that the system's reserve margin was insufficient to fully absorb - in this state, the priority of system operators shifts to taking corrective emergency control actions (generation redispatch, load shedding, reactive power support adjustments, or switching operations) as quickly as possible to relieve the limit violations and restore the system to a normal (or at least a stable, non-violating) operating condition, since continued operation in the emergency state risks further equipment damage or escalation into a wider cascading failure and eventual blackout.

The restorative operating state occurs after a partial or complete system blackout (loss of supply to some or all of the system), during which system operators are actively working to re-energize de-energized parts of the network and restore service to affected customers, typically through a carefully planned, staged restoration sequence (starting with black-start-capable generating units that can start without external power, gradually re-energizing transmission paths and bringing additional generation and load back online in a controlled sequence) - this restorative process must be carried out carefully and gradually, since attempting to restore too much load or too many transmission paths simultaneously, before adequate generation and voltage control capability has been re-established, risks triggering a repeat collapse of the partially-restored system.

It is also worth noting how the three power system operating states described in part (b) relate directly to the voltage control techniques discussed in part (a): tap changing transformers, together with the reactive power compensation devices examined elsewhere in this examination (shunt and series capacitors, STATCOM, SVC), are among the primary tools system operators rely on to keep the system within its normal operating state under everyday load variation, while their more aggressive or rapid deployment (switching in additional capacitor banks, adjusting tap positions more assertively) often forms part of the corrective actions taken during an emergency operating state to relieve voltage violations before they escalate into a wider system disturbance.

Recognizing this connection between everyday voltage-control equipment and the broader operating-state framework helps a student appreciate why these topics are so often taught and examined together within a single power system operation and control course unit.

Together, these voltage-control and operating-state concepts form a coherent picture of how power system operators maintain reliable service under everyday and abnormal conditions alike.

Back to Paper