RTUEE / EC / EEEYr 2019 · Sem 72019

Q6Power System Analysis

Question

16 marks

3. (a) What do you understand by symmetrical components? Explain positive, negative and zero sequence components. [8]

(b) Derive expression for fault current by symmetrical component method for single line to ground fault. [8]

Answer

(a) Symmetrical Components - Positive, Negative and Zero Sequence

Symmetrical components (Fortescue's theorem) is a mathematical technique that decomposes any set of three unbalanced three-phase phasors (voltages or currents) into a sum of three balanced (symmetrical) three-phase phasor sets: a positive-sequence set, a negative-sequence set, and a zero-sequence set - since analyzing a balanced three-phase network under balanced sequence excitation reduces to a simple single-phase (per-phase) equivalent circuit calculation, this decomposition allows any unbalanced fault or loading condition to be analyzed as the superposition of three independent, individually balanced sub-problems, each solvable with familiar single-phase circuit techniques, rather than requiring a full three-phase coupled-circuit solution directly.

The positive-sequence component consists of three phasors equal in magnitude, displaced 120 degrees from each other, and having the same phase sequence (rotation order) as the original, normal balanced supply (typically a-b-c) - this positive-sequence set represents the balanced, 'normal' three-phase quantity that would exist if the system were perfectly balanced, and it is this component that is primarily responsible for producing the normal, useful rotating magnetic field and torque in three-phase rotating machines.

The negative-sequence component also consists of three phasors equal in magnitude and displaced 120 degrees from each other, but with the opposite phase sequence (rotation order, a-c-b instead of a-b-c) compared to the positive-sequence set - in a rotating machine, negative-sequence currents produce a magnetic field rotating in the opposite direction to the positive-sequence field and to the rotor's actual rotation, inducing double-frequency currents in the rotor and causing additional heating, vibration, and a retarding torque component, which is why negative-sequence current is generally undesirable and is limited by protective relaying (negative-sequence overcurrent protection) in practical power systems.

The zero-sequence component consists of three phasors that are equal in magnitude AND in phase with each other (zero degrees displacement, unlike the 120-degree displacement of the positive- and negative-sequence sets) - because all three zero-sequence phase currents are identical in both magnitude and phase, they sum to three times a single phase's zero-sequence value rather than canceling, meaning zero-sequence current requires a physical return path (a grounded neutral connection, or an internally circulating path such as a delta winding) to flow at all; zero-sequence current is entirely absent in any three-wire (no neutral connection) three-phase system or fault type, appearing specifically in faults and system configurations involving a ground/neutral return path, such as the single line-to-ground fault examined in the second part of this question.

(b) Fault Current for Single Line-to-Ground Fault by Symmetrical Component Method

Sequence Networks in Series - LG FaultPositive seq (E, X1)Negative seq (X2)Zero seq (X0)

For a single line-to-ground (LG) fault on phase-a at a bus in a system with pre-fault positive-sequence internal EMF E, and sequence reactances X1 (positive), X2 (negative), and X0 (zero), with fault impedance Zf (commonly taken as zero for a solid fault): the boundary conditions at the fault point are Ib=0, Ic=0 (only phase-a carries fault current), and Va=Zf*Ia (the fault-point voltage on the faulted phase equals the fault impedance drop).

Applying the symmetrical component transformation to the boundary condition Ib=Ic=0 shows that the three sequence currents must all be equal: I0=I1=I2 - this is the single most important and distinctive characteristic condition of the single line-to-ground fault (compare with the line-to-line fault, where I0=0 and I1=-I2, examined elsewhere in this examination), and it is this equal-sequence-current condition that dictates the three sequence networks must be connected in series (rather than in the parallel-type connection used for a line-to-line fault) to correctly represent the LG fault boundary conditions.

Since the actual fault current in phase a is Ia = I0+I1+I2 = 3*I1 (using the equal-sequence-current result just derived), the final expression for the single line-to-ground fault current is:

For the common special case of a solidly grounded fault (Zf=0), this simplifies further to Ia=3E/(X1+X2+X0). It is worth noting that if X0 happens to be smaller than X1 (which can occur, for instance, near a solidly-grounded generator or transformer with a comparatively low zero-sequence impedance path), the resulting single line-to-ground fault current 3E/(X1+X2+X0) can actually exceed the corresponding three-phase fault current E/X1 - this is precisely the underlying reason, examined further elsewhere in this examination, why a single line-to-ground fault at an alternator's terminals can, under such conditions, be more severe (produce a larger fault current) than a three-phase fault at the same location, contrary to the common but not universally correct intuition that a three-phase fault is always the most severe fault type.

It is also worth noting why the symmetrical component method's core value lies specifically in reducing an unbalanced three-phase problem to three independent, individually-balanced single-phase-equivalent sub-problems: since positive-, negative-, and zero-sequence networks are, by the very construction of the symmetrical component transformation, mutually decoupled for any balanced (symmetrical) network element such as transmission lines, transformers, and rotating machines under normal balanced operation, each sequence network can be analyzed entirely independently using ordinary single-phase circuit techniques, with only the fault-point boundary conditions (differing for each fault type, as shown for both the single line-to-ground and line-to-line faults elsewhere in this examination) providing the specific coupling connections between the three otherwise-independent sequence networks.

It is further worth noting the practical protection-engineering significance of the single line-to-ground fault current expression derived here: because ground faults are by far the most common fault type on real power systems (as noted elsewhere in this examination), correctly predicting the single line-to-ground fault current magnitude and its dependence on the zero-sequence reactance X0 (and any neutral grounding impedance) is essential for properly setting ground-fault protective relay pickup thresholds and coordination margins throughout a power system, making the symmetrical-component-based LG fault derivation presented here one of the single most practically important calculations in the entire discipline of power system fault analysis and protection coordination.

In summary, the symmetrical component technique's core value - decomposing an unbalanced problem into three independently-solvable balanced sub-problems, connected together only through fault-type-specific boundary conditions at the point of unbalance - together with the specific single line-to-ground fault derivation shown here, illustrate the general analytical framework that underlies essentially all unsymmetrical fault analysis examined throughout this examination.

Mastering both the conceptual meaning of positive, negative, and zero sequence quantities and the specific fault-current derivation technique for a given fault type equips a power engineer to extend the identical analytical approach to the remaining unsymmetrical fault types not explicitly derived here, such as the double line-to-ground fault.

Back to Paper