Q2Power System Protection
Question
Q.2. Explain different types of over-current relay co-ordination in detail.
Answer
Over-current relay coordination is achieved through current grading (using different pick-up settings for relays at different network locations), time grading (using progressively longer time delays for relays closer to the source), and a combination of both (using inverse-time characteristics), ensuring that the relay closest to a fault operates first while relays further upstream provide graded back-up.
Types of Over-Current Relay Coordination
Over-current relay coordination refers to the systematic selection of pick-up current settings and/or time-delay settings for a series of overcurrent relays positioned at successive points along a radial (or, with more elaborate schemes, networked) power system, such that for a fault occurring anywhere in the system, the relay-breaker combination closest to (electrically nearest) the fault operates first, isolating the smallest possible affected section, while relays further upstream (toward the source) remain deliberately delayed, providing back-up protection only if the nearer relay/breaker fails to clear the fault.
Current Grading
Current grading achieves selectivity by setting the pick-up (operating) current of successive relays progressively higher for relays located closer to the source, exploiting the fact that fault current magnitude in a radial system generally decreases as fault location moves further from the source (due to the increasing cumulative impedance between source and a more distant fault point) — a relay set to pick up only above a certain current threshold will then only operate for faults occurring within its own zone (where fault current exceeds its setting) and will remain stable for a fault further downstream (where the reduced fault current falls below its setting, but is still above the setting of the relay actually protecting that downstream zone). Current grading alone, however, is generally difficult to apply reliably in practice, since fault current levels can vary considerably depending on the specific system operating configuration and fault type, making it hard to guarantee an adequate margin between successive relay settings across all possible operating conditions using current magnitude alone.
Time Grading
Time grading achieves selectivity by assigning a progressively longer deliberate time delay to relays located further from the fault point (closer to the source), typically using a fixed, definite-time delay setting for each relay along the radial feeder, incrementing by a suitable time margin (commonly 0.3 to 0.5 seconds, accounting for circuit breaker interrupting time, relay overshoot, and a safety margin) between each successive relay moving toward the source — this ensures the relay closest to the fault, having the shortest time delay, operates and clears the fault first, before any upstream relay's longer time delay has elapsed, with each upstream relay serving as back-up only if the nearer relay/breaker fails to operate within its own allotted time. A key drawback of pure time grading (using definite-time relays throughout) is that relays closest to the source (which must have the longest cumulative time delay to maintain coordination across many series-connected zones) take a correspondingly long time to clear a fault occurring near the source itself, even though such faults are typically the most severe in magnitude — a significant disadvantage when many relay zones must be coordinated in series.
Combined Current and Time Grading (Inverse-Time Overcurrent Relays)
The most widely used practical coordination approach combines both current and time grading using inverse-definite-minimum-time (IDMT) relay characteristics, in which each relay's operating time is not fixed but varies inversely with the magnitude of fault current — operating faster for larger fault currents and slower for smaller fault currents (closer to its pick-up threshold). This inverse-time characteristic is particularly advantageous because a fault occurring closer to the source (producing a higher fault current, since less line impedance separates the fault from the source) is cleared more quickly by the relay closest to that fault (which sees the largest current for its own zone), even though that same relay, being positioned closer to the source, must still maintain an overall coordinated time margin relative to relays further downstream — the inverse characteristic allows this coordination margin to be achieved without requiring excessively long fixed clearing times at the source end for lower-magnitude faults, striking a practical balance between the selectivity benefits of current grading and the coordination benefits of time grading, and making IDMT relay coordination (using standard normal-inverse, very-inverse, or extremely-inverse characteristic curves, selected according to the specific system's fault-current-versus-distance profile) the standard overcurrent protection coordination approach used throughout radial distribution and sub-transmission network protection in practice.