RTUEE / EC / EEEYr 2022 · Sem 52022

Q5Power System - I

Question

15 marks

Q.5. Write note on the followings protection schemes with their application: (a) Over-current (b) Directional protection (c) Distance protection (d) Differential protection

Answer

Over-current protection trips on excessive current magnitude; directional protection adds current-direction discrimination to distinguish faults in front of vs behind the relay; distance protection measures line impedance (proportional to fault distance) to provide zone-graded protection for transmission lines; and differential protection compares currents entering and leaving a protected zone, tripping instantly on any internal imbalance — each is applied to specific equipment/network configurations.

(a) Over-Current Protection

Over-current protection operates by comparing the measured current magnitude against a preset pickup value; if the current exceeds this threshold, the relay operates after an intentional time delay (definite-time or inverse-time characteristic, such as IDMT — Inverse Definite Minimum Time), allowing coordination (grading) between relays at successive points in a radial network so that only the relay nearest to the fault trips first. Application: widely used for protection of radial distribution feeders, transformers (as backup protection), and as backup protection for transmission lines, due to its simplicity and low cost, though it does not inherently distinguish fault direction or provide precise fault location.

(b) Directional Protection

Directional protection adds a directional element to over-current protection, using the phase relationship between the measured current and a reference (polarizing) voltage or current to determine whether the fault lies in the 'forward' (protected) direction or the 'reverse' direction; the relay is designed to operate only for faults in the specified direction, remaining restrained for faults in the opposite direction. Application: essential in networks with multiple sources or ring/meshed configurations, parallel feeders, and interconnected systems, where fault current can flow in either direction through a given relay location depending on which source is feeding the fault, and non-directional over-current relays alone cannot provide correct selective tripping.

(c) Distance Protection

Distance protection measures the apparent impedance (Z = V/I, computed from the measured voltage and current at the relay location) looking into the protected line; since line impedance is proportional to physical distance along a uniform conductor, the measured impedance directly indicates how far along the line the fault has occurred. The relay's characteristic (commonly represented as a circle or polygon on the R-X impedance plane, e.g., mho or quadrilateral characteristics) is set to operate for faults within specific graded zones — Zone 1 (typically 80-90% of the protected line, instantaneous trip), Zone 2 (up to 120-150% of the line, covering the remaining line plus a safety margin, with a short time delay) and Zone 3 (extending further into the next line section, providing remote backup, with a longer time delay). Application: the standard primary protection scheme for medium- and high-voltage transmission lines, since it provides fast, selective tripping without needing communication between relays at each end (though communication-aided schemes like permissive overreach transfer trip further improve speed and selectivity).

(d) Differential Protection

Differential protection compares the currents entering and leaving a clearly defined protected zone (using current transformers at each boundary of the zone) using Kirchhoff's current law: under normal (or external fault) conditions, the phasor sum of entering and leaving currents is ideally zero (or matches within a small restraining margin, accounting for CT errors); for any fault within the protected zone, this balance is disrupted, and the resulting differential current causes the relay to operate. Because differential protection depends only on currents at the boundary of its own protected zone (and not on relays or settings elsewhere in the network), it is inherently fast (can trip instantaneously) and unit-selective (responds only to faults strictly inside its protected zone), requiring no time-grading with adjacent protection. Application: widely used for protecting transformers, generators, busbars, and short transmission lines/feeders (pilot-wire or communication-based differential schemes), wherever the cost of running dedicated communication/pilot channels between the zone's boundary CTs is justified by the need for very fast, precise fault clearance in critical equipment.

Additional Detail: IDMT Characteristics and Relay Coordination for Over-Current Protection

Inverse Definite Minimum Time (IDMT) over-current relays are characterized by the standard equation:

where I is the fault current, Is is the relay's plug/pickup setting, k and α are constants defining the specific curve shape (Normal Inverse, Very Inverse, Extremely Inverse, per IEC/IEEE standards), and TMS (Time Multiplier Setting) scales the entire curve. Grading between successive relays along a radial feeder is achieved by setting each relay's TMS/pickup so that the relay nearest the fault operates first, with a coordination time interval (typically 0.3-0.5 s, accounting for breaker interrupting time and relay/CT errors) built in before the next upstream relay would operate — this graded time-current coordination is what allows a chain of purely time-graded over-current relays to achieve selective tripping without any inter-relay communication, at the cost of the relays furthest from the source experiencing progressively longer fault-clearance times.

Additional Detail: Directional Element Polarization Choices

A directional relay requires a stable polarizing reference against which to measure the operating current's phase angle; common choices include the faulted phase's own voltage (self-polarization, which becomes unreliable very close to a bolted three-phase fault where the local voltage collapses to near zero), a healthy-phase or cross-phase voltage combination (cross-polarization, maintaining a usable reference voltage even during a close-in fault on the polarizing phase itself), and, for ground-fault directional elements specifically, the zero-sequence (residual) voltage or a voltage derived from a broken-delta VT secondary connection, since genuine zero-sequence quantities exist only during unbalanced (ground) faults and provide a clean directional reference uncontaminated by load current or balanced fault conditions.

Additional Detail: Distance Relay Characteristics and Power Swing Blocking

The choice of distance relay characteristic shape on the R-X plane materially affects its performance: a simple impedance (circular, non-directional) characteristic is the oldest and simplest but requires a separate directional element to avoid mal-operation for reverse faults; the mho characteristic (a circle passing through the origin, inherently directional since it responds only to impedance within its forward-offset circle) is widely used for phase-fault distance protection; and quadrilateral characteristics (independently adjustable reach and resistive blinders) offer better discrimination for high-resistance ground faults, which a simple mho circle may under-reach for. A further important practical consideration is power swing blocking: during a large disturbance elsewhere in the system, the resulting swing in the power angle between two areas can cause the apparent impedance measured by a distance relay to transiently pass through its protected zones even though no actual fault exists, and dedicated power-swing detection/blocking logic (based on the rate of change of measured impedance, which is much slower for a genuine swing than for an actual fault) is used to prevent unwanted tripping during stable or even unstable power swings that are not themselves faults requiring that particular line to trip.

Additional Detail: CT Requirements and Bias (Restraint) in Differential Protection

Practical differential protection schemes almost always include a restraint (bias) characteristic rather than a simple, unbiased current-difference comparison, because real current transformers at the two ends of a protected zone are never perfectly identical or free of saturation, and even small CT ratio/phase errors under heavy external (through) fault current can otherwise produce a spurious differential signal large enough to cause false tripping. A percentage-biased (or 'slope') differential characteristic compares the differential current against a restraining current proportional to the through-current magnitude, requiring proportionally larger differential current to trip as the through-fault current increases, thereby maintaining security against external faults with CT mismatch while still retaining high sensitivity and speed for genuine internal faults, where the differential current is a large fraction of the total current rather than a small mismatch-driven residual.

Back to Paper