Q2Electrical Machines II

Question

10 marks

Find the synchronous impedance, synchronous reactance and the terminal voltage when full load is thrown off, Of a , , alternator, in which a given field current produces an armature current of on short circuit and a generated e.m.f. of on open circuit. The armature resistance is .

Answer

Calculation of synchronous impedance, reactance, and terminal voltage regulation for a 6600V alternator using the EMF method.

Assume the given is the terminal line voltage of a 3-phase, star-connected alternator. Terminal Phase voltage . Given: Full load armature current , Power factor lagging (). Armature resistance .

For a specific field current, Open Circuit line voltage is . So, Open Circuit Phase voltage . The corresponding Short Circuit current .

1. Synchronous Impedance (): .

2. Synchronous Reactance (): .

3. Terminal Voltage when full load is thrown off (): This requires finding the internal induced phase EMF, , which becomes the terminal voltage on no-load. Using the EMF equation for a lagging power factor:

.

The line EMF when load is thrown off is .